| Failure
can in effect give your insurance company a good reason not to pay-out
in an incident as well as not meeting your Health & Safety requirements.
TTS Fire & Security Ltd.
have a maintenance plan to suit at reasonable rates and we don't tie you in
to long term contracts. Quite simply we ask you to sign a non binding 12
month contract instructing us to carry out the service. We then carry
out the work to your complete satisfaction and issue a work sheet and
compliance certificate if your system is compliant.
We are able to undertake
all aspects of maintaining your equipment within the UK including Emergency
Lighting and Fire Extinguishers. Overseas we offer to provide training
so that you are fully conversant with all aspects of keeping your system
fully operational to local requirements and legislation. TTS Fire
& Security Ltd. also maintain and service existing conventional "hard
wired" fire alarm systems within the UK. We hold spares of Gent, Apollo,
Ziton, KAC, etc. All fire systems maintained to BS 5839. Remember as a
condition of meeting BS 5839 Part 1 the system must be regularly inspected
and maintained at least every 6 months. This is in addition to duties
required by the system user. See our BS 5839 definition guide A guide to
BS
5839.
BS5839: Part 1: 2002 TESTING
AND MAINTENANCE
DAILY INSPECTION
Check that the Charger On
indicator shows. Inspect for any fault indicator showing or sounder operating.
Inform the designated responsible person of any fault.
WEEKLY TEST
Ensure that all indicators
show by resetting according to the instructions provided with the panel
and check that the internal sounder operates. Operate a call point or detector
to test the system. Check that the sounders operate. Reset the fire alarm
panel. Each week choose a different zone in rotation, so that way all call
points are tested in rotation. Check all call points and detectors and
ensure that none are obstructed in any way. Enter results of tests into
log book.
SIX MONTHLY TEST
Check all previous log book
entries and clarify that any remedial action has been taken. Check the
battery and its connections. Operate a call point or detector in each zone
to test the fire alarm as per above. Remove mains supply and check that
the battery is capable of supplying the alarm sounders.
ANNUAL TEST
As per above. Additionally
test all detectors and call points and check for operation.
EVERY 2 - 3 YEARS
Clean smoke detectors to
ensure correct operation and freedom from false alarms. Special equipment
is required for cleaning smoke detectors.
EVERY 4 YEARS
Replace sealed lead acid
batteries. If the operating temperature exceeds 25oC continuously, then
the battery may need to be replaced sooner.